Infrared point detector with HART and Modbus outputs in stainless housing.
Designed to
| Range | 0–100% LEL CH4 |
|---|---|
| Outputs | 4–20 mA, HART, Modbus |
| Housing | SS316 |
| Standards | ATEX/IECEx Ex d; IEC 61508 SIL 2; EN 60079-29-1 |
Infrared point detector with HART and Modbus outputs in stainless housing.
Specifications and certification details are confirmed in the quotation against the manufacturer's current datasheet. Contact our team for sizing, alternatives and documentation requirements.
ATEX — EU ATEX Directive 2014/34/EU: equipment for potentially explosive atmospheres
EU legal requirement for equipment used where flammable gas, vapour or dust may be present. Equipment must be certified for the zone and gas group of the area where it is used.
Reading the marking: Ex symbol, Group II (surface industry), category 1 (Zone 0/20), 2 (Zone 1/21) or 3 (Zone 2/22), G gas or D dust. Protection concept, e.g. Ex ia (intrinsic safety), Ex d (flameproof), Ex e (increased safety). Gas group IIA, IIB, IIC (IIC most demanding, includes hydrogen). Temperature class T1-T6 (T6 lowest surface temperature).
IECEx — IEC System for certification to standards relating to equipment for use in explosive atmospheres
International certification scheme based on the IEC 60079 series; certificates can be checked on the IECEx online database. Many Middle East authorities accept IECEx or ATEX certification.
Reading the marking: Uses the same Ex marking as ATEX, e.g. Ex ia IIC T4 Ga, with Equipment Protection Level Ga/Gb/Gc.
IEC 61508 — Functional safety of electrical/electronic/programmable electronic safety-related systems
Framework for safety-critical instruments. A SIL rating shows the device can be used in a safety function of that integrity level, subject to the overall system design.
Reading the marking: SIL 1 to SIL 4 (highest). Gas detection and fire equipment is typically SIL 2 or SIL 3 capable.
EN 60079-29-1 — Explosive atmospheres: gas detectors, performance requirements of detectors for flammable gases
Covers the measuring accuracy, response time and stability of flammable gas detectors, usually reading in % LEL.