

Acoustic detector that senses airborne ultrasound from pressurised gas leaks regardless of wind direction.
Designed to
| Detection radius | Up to 20 m |
|---|---|
| Frequency range | 25–100 kHz |
| Outputs | 4–20 mA, relays, Modbus |
| Housing | SS316 |
| Standards | ATEX/IECEx; IEC 61508 SIL 2 |
Acoustic detector that senses airborne ultrasound from pressurised gas leaks regardless of wind direction.
Specifications and certification details are confirmed in the quotation against the manufacturer's current datasheet. Contact our team for sizing, alternatives and documentation requirements.
ATEX — EU ATEX Directive 2014/34/EU: equipment for potentially explosive atmospheres
EU legal requirement for equipment used where flammable gas, vapour or dust may be present. Equipment must be certified for the zone and gas group of the area where it is used.
Reading the marking: Ex symbol, Group II (surface industry), category 1 (Zone 0/20), 2 (Zone 1/21) or 3 (Zone 2/22), G gas or D dust. Protection concept, e.g. Ex ia (intrinsic safety), Ex d (flameproof), Ex e (increased safety). Gas group IIA, IIB, IIC (IIC most demanding, includes hydrogen). Temperature class T1-T6 (T6 lowest surface temperature).
IECEx — IEC System for certification to standards relating to equipment for use in explosive atmospheres
International certification scheme based on the IEC 60079 series; certificates can be checked on the IECEx online database. Many Middle East authorities accept IECEx or ATEX certification.
Reading the marking: Uses the same Ex marking as ATEX, e.g. Ex ia IIC T4 Ga, with Equipment Protection Level Ga/Gb/Gc.
IEC 61508 — Functional safety of electrical/electronic/programmable electronic safety-related systems
Framework for safety-critical instruments. A SIL rating shows the device can be used in a safety function of that integrity level, subject to the overall system design.
Reading the marking: SIL 1 to SIL 4 (highest). Gas detection and fire equipment is typically SIL 2 or SIL 3 capable.
Images may be representative of the product type; specifications and standards are indicative. Final specification, certification and suitability for your application are confirmed in our written quotation and the manufacturer’s instructions for use.
Complete the solution



FeaturedFixed Gas DetectionGD-FX-205
ATEX/IECEx · EN 60079-29-1
Send us your full list with quantities and delivery location — we’ll quote every line with documentation.